SEG XE2
XE2 Loss of Excitation

Loss of Excitation - Generator DC exciter current supervision, over-, undercurrent and diode failure detection. 0 - 300 Hz, Exciter overcurrent: I> = 0 - 15 A (min 0,2 A) tI> = 0 - 5 s / 0 - 50 s; Exciter undercurrent: I< = 0 - 5 A (min 0,2 A) tI< = 0 - 5 s / 0 - 50 s; Diode Failure detection: IR> 0 - 125 % (min 10 %)

FEATURES & FUNCTIONALITY

Loss of Excitation - Generator DC exciter current supervision, over-, undercurrent and diode failure detection. 0 - 300 Hz

The relay XE2 of the easy PROFESSIONAL LINE is used for supervision of the exciter current. By the exciter current element the direct current of the excitation machine in brushless machines is supervised. The protection function includes detection of overcurrent and undercurrent as well as supervision of the ripple component of the exciter current and so faults of the rotating diodes would be revealed.

The XE2 is compliant with IEC 60255-1.

Benefits of the Professional Line

Fast DIN rail mounting ⇛ easy and fast mounting
Sealable plastic covers ⇛ safe (see if anybody has broken the seal)
Super easy settings via front buttons ⇛ fast without computer
LED and output relays fault indication ⇛ easy to find out what has happened
Compact form factor ⇛ fits in small spaces
IT security ⇛ no way to attack via Ethernet
Robust and reliable ⇛ well proven reliable quality
Wide Range Power Supply ⇛ don’t worry about available supply voltage
Integrated Self-Test Procedure (via button) ⇛ fast and easy checks: relays, LEDs