SEG XI1-1A
XI1 Phase Overcurrent 1A

1A, DIN Rail, DEFT, NINV, VINV, EINV, ANSI 50, 51, IEC 60255-1, 250 x In (half cycle), 100 x In for 1s, 30 x In for 10 s, 4 x In continuous

FEATURES & FUNCTIONALITY

Phase Overcurrent 1A, DIN Rail, DEFT, NINV, VINV, EINV, ANSI 50, 51, IEC 60255-1, 250 x In (half cycle), 100 x In for 1s, 30 x In for 10 s, 4 x In continuous.

Basic time delay accuracy:

0.5 % or ±25 ms,
Basic accuracy of current: ±3 % of the setting value,
Accuracy of time delay in the range of 2 - 20 x IS: 2 % DEFT/5 % NINV and VINV/7,
5 % EINV/or 25 ms